Back to the list of connectors

Eaton PDU (SNMP)

Description

This connector provides hardware monitoring through Eaton PDU SNMP interface. Data gathered includes temperature, inlet/outlet voltages, and power consumption.

Connector ID: EatonPDU

Target

Typical platform: Eaton PDU

Operating system: Out-of-Band

Prerequisites

Leverages: PDU SNMP Enabled

Technology and protocols: SNMP

This connector is not available for the local host (it is applicable to remote hosts only).

Examples

CLI

hws HOSTNAME -t management -f EatonPDU --snmp v2c --community public

hws-config.yaml

hosts:
- host:
    hostname: <HOSTNAME> # Change with actual host name
    type: management
  selectedConnectors: [ EatonPDU ] # Optional, to load only this connector
  snmp:
    version: v1 # Read documentation for v2 and v3
    community: public # or probably something more secure

Connector Activation Criteria

The Eaton PDU (SNMP) connector will be automatically activated, and its status will be reported as OK if all the below criteria are met:

  • An SNMP Get on the OID 1.3.6.1.4.1.534.6.6.7.1.2.1.3.0 must return a value that matches with the . regular expression

Metrics

Type Collected Metrics Specific Attributes (Labels)
Enclosure
  • hw.enclosure.energy
  • hw.status{hw.type="enclosure",state="ok|degraded|failed"}
  • hw.status{hw.type="enclosure",state="present"}
  • info
  • model
  • serial_number
  • type
  • vendor
Temperature Sensor
  • hw.status{hw.type="temperature",state="present"}
  • hw.temperature
  • hw.temperature.limit{limit_type="high.critical"}
  • hw.temperature.limit{limit_type="high.degraded"}
  • sensor_location
Voltage Sensor
  • hw.status{hw.type="voltage",state="present"}
  • hw.voltage
  • hw.voltage.limit{limit_type="high.critical"}
  • hw.voltage.limit{limit_type="low.critical"}
    No results.