Back to the list of connectors
Generic UPS
Description
This connector provides hardware monitoring of MIB-2 Standard UPS through an SNMP interface.
Connector ID: GenericUPS
This connector is superseded by:
Target
Typical platform: Any UPS which supports UPS-MIB (RFC1628)
Operating system: Out-of-Band
Prerequisites
Leverages:
Technology and protocols: SNMP
This connector is not available for the local host (it is applicable to remote hosts only).
Examples
CLI
hws HOSTNAME -t management -f GenericUPS --snmp v2c --community public
hws-config.yaml
hosts:
- host:
hostname: <HOSTNAME> # Change with actual host name
type: management
selectedConnectors: [ GenericUPS ] # Optional, to load only this connector
snmp:
version: v1 # Read documentation for v2 and v3
community: public # or probably something more secure
Connector Activation Criteria
The Generic UPS connector will be automatically activated, and its status will be reported as OK if all the below criteria are met:
- An SNMP Get-Next on the OID
1.3.6.1.2.1.33
must return a value in the same subtree
Metrics
Type | Collected Metrics | Specific Attributes (Labels) |
---|---|---|
Enclosure |
|
|
Battery |
|
|
Temperature Sensor |
|
|
Voltage Sensor |
|
|
Search Results for {{siteSearch | truncate:'50'}}
{{resultArray.length}}
No results.